Pressureless systems

If water is no longer economical as a heat transfer fluid, hydrocarbon-based fluids can be used with a boiling point above the maximum bulk temperature.

There are a large number of products, some of which differ greatly in their thermal and oxidative stability and maximum bulk and film temperature, as well as in their safety and environment-related properties and thermodynamic material data, such as viscosity and boiling point.

 

back to overview

Areas of application

  • Temperature control systems
  • Reactor heating and cooling
  • Heat recovery
  • Continuous and intermittent heating processes
  • Thermal control of extruders
  • Heat dissipation in exothermal reactions
  • Waterless reaction processes

Our heat transfer media are suitable for this area of application:

FRAGOLTHERM® 660
FRAGOLTHERM® 660

FRAGOLTHERM® 660

Dichte 20 °C:
Density 20 °C:
1008 kg/m³
Kin. Viskosität 40 °C:
Kin. viscosity 40 °C:
30,39 mm²/s
Pourpoint:
Pour Point:
-24 °C
Untere Einsatzgrenze:
Minimal operating temperature:
0 °C
Vorlauftemperatur max.:
Bulk temperature max.:
355 °C
Filmtemperatur max.:
Film temperature max.:
380 °C
Siedebeginn:
Boiling Point:
360 °C
Flammpunkt:
Flash Point:
175 °C
Wassergefährdungsklasse:
Water hazard classification:
2
Freigaben:
Approval:
-
0 °C
355 °C
FRAGOLTHERM® HT
FRAGOLTHERM® HT

FRAGOLTHERM® HT

Dichte 20 °C:
Density 20 °C:
1044 kg/m³
Kin. Viskosität 40 °C:
Kin. viscosity 40 °C:
16,96 mm²/s
Pourpoint:
Pour Point:
-34 °C
Untere Einsatzgrenze:
Minimal operating temperature:
0 °C
Vorlauftemperatur max.:
Bulk temperature max.:
350 °C
Filmtemperatur max.:
Film temperature max.:
380 °C
Siedebeginn:
Boiling Point:
390 °C
Flammpunkt:
Flash Point:
200 °C
Wassergefährdungsklasse:
Water hazard classification:
3
Freigaben:
Approval:
-
0 °C
350 °C
FRAGOLTHERM® 620
FRAGOLTHERM® 620

FRAGOLTHERM® 620

Dichte 20 °C:
Density 20 °C:
951 kg/m³
Kin. Viskosität 40 °C:
Kin. viscosity 40 °C:
10,8 mm²/s
Pourpoint:
Pour Point:
<-40 °C
Untere Einsatzgrenze:
Minimal operating temperature:
-12 °C
Vorlauftemperatur max.:
Bulk temperature max.:
330 °C
Filmtemperatur max.:
Film temperature max.:
355 °C
Siedebeginn:
Boiling Point:
332 °C
Flammpunkt:
Flash Point:
162 °C
Wassergefährdungsklasse:
Water hazard classification:
2
Freigaben:
Approval:
-
-12 °C
330 °C
FRAGOLTHERM® Q-HTF
FRAGOLTHERM® Q-HTF

FRAGOLTHERM® Q-HTF

Dichte 20 °C:
Density 20 °C:
858 kg/m³
Kin. Viskosität 40 °C:
Kin. viscosity 40 °C:
35,36 mm²/s
Pourpoint:
Pour Point:
-18 °C
Untere Einsatzgrenze:
Minimal operating temperature:
-18 °C
Vorlauftemperatur max.:
Bulk temperature max.:
325 °C
Filmtemperatur max.:
Film temperature max.:
343 °C
Siedebeginn:
Boiling Point:
380 °C
Flammpunkt:
Flash Point:
245 °C
Wassergefährdungsklasse:
Water hazard classification:
1
Freigaben:
Approval:
-
-18 °C
325 °C
FRAGOLTHERM® Q-32-N
FRAGOLTHERM® Q-32-N

FRAGOLTHERM® Q-32-N

Dichte 20 °C:
Density 20 °C:
871 kg/m³
Kin. Viskosität 40 °C:
Kin. viscosity 40 °C:
31,00 mm²/s
Pourpoint:
Pour Point:
-12 °C
Untere Einsatzgrenze:
Minimal operating temperature:
-12 °C
Vorlauftemperatur max.:
Bulk temperature max.:
320 °C
Filmtemperatur max.:
Film temperature max.:
340 °C
Siedebeginn:
Boiling Point:
360 °C
Flammpunkt:
Flash Point:
220 °C
Wassergefährdungsklasse:
Water hazard classification:
1
Freigaben:
Approval:
-
-12 °C
320 °C
FRAGOLTHERM® Q-32-A
FRAGOLTHERM® Q-32-A

FRAGOLTHERM® Q-32-A

Dichte 20 °C:
Density 20 °C:
871 kg/m³
Kin. Viskosität 40 °C:
Kin. viscosity 40 °C:
31,00 mm²/s
Pourpoint:
Pour Point:
-12 °C
Untere Einsatzgrenze:
Minimal operating temperature:
-12 °C
Vorlauftemperatur max.:
Bulk temperature max.:
320 °C
Filmtemperatur max.:
Film temperature max.:
340 °C
Siedebeginn:
Boiling Point:
360 °C
Flammpunkt:
Flash Point:
220 °C
Wassergefährdungsklasse:
Water hazard classification:
1
Freigaben:
Approval:
-
-12 °C
320 °C
FRAGOLTHERM® Q-AF
FRAGOLTHERM® Q-AF

FRAGOLTHERM® Q-AF

Dichte 20 °C:
Density 20 °C:
851 kg/m³
Kin. Viskosität 40 °C:
Kin. viscosity 40 °C:
30,70 mm²/s
Pourpoint:
Pour Point:
<-18 °C
Untere Einsatzgrenze:
Minimal operating temperature:
-18 °C
Vorlauftemperatur max.:
Bulk temperature max.:
300 °C
Filmtemperatur max.:
Film temperature max.:
315 °C
Siedebeginn:
Boiling Point:
349 °C
Flammpunkt:
Flash Point:
204 °C
Wassergefährdungsklasse:
Water hazard classification:
1
Freigaben:
Approval:
-
-18 °C
300 °C
FRAGOLTHERM® Q-7
FRAGOLTHERM® Q-7

FRAGOLTHERM® Q-7

Dichte 20 °C:
Density 20 °C:
830 kg/m³
Kin. Viskosität 40 °C:
Kin. viscosity 40 °C:
7,27 mm²/s
Pourpoint:
Pour Point:
-48 °C
Untere Einsatzgrenze:
Minimal operating temperature:
-48 °C
Vorlauftemperatur max.:
Bulk temperature max.:
270 °C
Filmtemperatur max.:
Film temperature max.:
285 °C
Siedebeginn:
Boiling Point:
305 °C
Flammpunkt:
Flash Point:
170 °C
Wassergefährdungsklasse:
Water hazard classification:
1
Freigaben:
Approval:
-
-48 °C
270 °C
FRAGOLTHERM® FG-35
FRAGOLTHERM® FG-35

FRAGOLTHERM® FG-35

Dichte 20 °C:
Density 20 °C:
861 kg/m³
Kin. Viskosität 40 °C:
Kin. viscosity 40 °C:
35,40 mm²/s
Pourpoint:
Pour Point:
-15 °C
Untere Einsatzgrenze:
Minimal operating temperature:
-15 °C
Vorlauftemperatur max.:
Bulk temperature max.:
325 °C
Filmtemperatur max.:
Film temperature max.:
345 °C
Siedebeginn:
Boiling Point:
>340 °C
Flammpunkt:
Flash Point:
245 °C
Wassergefährdungsklasse:
Water hazard classification:
1
Freigaben:
Approval:
HT1-Freigabe der NSF FDA 21 CFR Halal Kosher
-15 °C
325 °C
FRAGOLTHERM® FG-8
FRAGOLTHERM® FG-8

FRAGOLTHERM® FG-8

Dichte 20 °C:
Density 20 °C:
830 kg/m³
Kin. Viskosität 40 °C:
Kin. viscosity 40 °C:
7,27 mm²/s
Pourpoint:
Pour Point:
-48 °C
Untere Einsatzgrenze:
Minimal operating temperature:
-48 °C
Vorlauftemperatur max.:
Bulk temperature max.:
270 °C
Filmtemperatur max.:
Film temperature max.:
285 °C
Siedebeginn:
Boiling Point:
305 °C
Flammpunkt:
Flash Point:
170 °C
Wassergefährdungsklasse:
Water hazard classification:
1
Freigaben:
Approval:
HT1-Freigabe der NSF FDA 21 CFR Halal Kosher
-48 °C
270 °C
FRAGOLTHERM® F-N
FRAGOLTHERM® F-N

FRAGOLTHERM® F-N

Dichte 20 °C:
Density 20 °C:
874 kg/m³
Kin. Viskosität 40 °C:
Kin. viscosity 40 °C:
16,5 mm²/s
Pourpoint:
Pour Point:
<-45 °C
Untere Einsatzgrenze:
Minimal operating temperature:
-10 °C
Vorlauftemperatur max.:
Bulk temperature max.:
300 °C
Filmtemperatur max.:
Film temperature max.:
340 °C
Siedebeginn:
Boiling Point:
348 °C
Flammpunkt:
Flash Point:
181 °C
Wassergefährdungsklasse:
Water hazard classification:
1
Freigaben:
Approval:
-
-10 °C
300 °C
FRAGOLTHERM® F-ADX10
FRAGOLTHERM® F-ADX10

FRAGOLTHERM® F-ADX10

Dichte 20 °C:
Density 20 °C:
857 kg/m³
Kin. Viskosität 40 °C:
Kin. viscosity 40 °C:
4,03 mm²/s
Pourpoint:
Pour Point:
-80 °C
Untere Einsatzgrenze:
Minimal operating temperature:
-56 °C
Vorlauftemperatur max.:
Bulk temperature max.:
250 °C
Filmtemperatur max.:
Film temperature max.:
280 °C
Siedebeginn:
Boiling Point:
293 °C
Flammpunkt:
Flash Point:
136 °C
Wassergefährdungsklasse:
Water hazard classification:
1
Freigaben:
Approval:
-
-56 °C
250 °C
FRAGOLTHERM® S-250
FRAGOLTHERM® S-250

FRAGOLTHERM® S-250

Dichte 20 °C:
Density 20 °C:
1.125 kg/m³
Kin. Viskosität 40 °C:
Kin. viscosity 40 °C:
41,15 mm²/s
Pourpoint:
Pour Point:
5 °C bis 8 °C
Untere Einsatzgrenze:
Minimal operating temperature:
5 °C
Vorlauftemperatur max.:
Bulk temperature max.:
250 °C
Filmtemperatur max.:
Film temperature max.:
260 °C
Siedebeginn:
Boiling Point:
n.a.
Flammpunkt:
Flash Point:
240 °C
Wassergefährdungsklasse:
Water hazard classification:
1
Freigaben:
Approval:
-
5 °C
250 °C
FRAGOLTHERM® S-20-A
FRAGOLTHERM® S-20-A

FRAGOLTHERM® S-20-A

Dichte 20 °C:
Density 20 °C:
1.034 kg/m³
Kin. Viskosität 40 °C:
Kin. viscosity 40 °C:
56,00 mm²/s
Pourpoint:
Pour Point:
-36 °C
Untere Einsatzgrenze:
Minimal operating temperature:
0 °C
Vorlauftemperatur max.:
Bulk temperature max.:
240 °C
Filmtemperatur max.:
Film temperature max.:
250 °C
Siedebeginn:
Boiling Point:
n.a.
Flammpunkt:
Flash Point:
>260 °C
Wassergefährdungsklasse:
Water hazard classification:
1
Freigaben:
Approval:
-
0 °C
240 °C
FRAGOLTHERM® S-15-A
FRAGOLTHERM® S-15-A

FRAGOLTHERM® S-15-A

Dichte 20 °C:
Density 20 °C:
1.013 kg/m³
Kin. Viskosität 40 °C:
Kin. viscosity 40 °C:
18,10 mm²/s
Pourpoint:
Pour Point:
-51 °C
Untere Einsatzgrenze:
Minimal operating temperature:
-13 °C
Vorlauftemperatur max.:
Bulk temperature max.:
205 °C
Filmtemperatur max.:
Film temperature max.:
215 °C
Siedebeginn:
Boiling Point:
n.a.
Flammpunkt:
Flash Point:
>220 °C
Wassergefährdungsklasse:
Water hazard classification:
1
Freigaben:
Approval:
-
-13 °C
205 °C
× We want to help!×

We look forward to your inquiry

Heat Transfer Fluids

Phone: +49 (0)208-300-02-50
Fax: +49 (0)208-300-02-33
Email: htffragol.de

Lubricants

Phone: +49 (0)208-300-02-40
Fax: +49 (0)208-300-02-77
Email: lubesfragol.de

Office

Phone: +49 (0)208-300-02-25
Fax: +49 (0)208-300-02-31
Email: rewefragol.de

Please use our contact form

For emergencies outside office hours:
+49 (0)208-300-02-99.